Cầu dao chống giật dòng Acti9 , 2P 25A 30ma
device location in system |
Outgoer
|
|
---|---|---|
network frequency |
50/60 Hz
|
|
[Ue] rated operational voltage |
220…240 V AC 50/60 Hz
|
|
residual current tripping technology |
Voltage independent
|
|
rated breaking and making capacity |
Idm 500 A
Im 500 A |
|
rated conditional short-circuit current |
GL63: Inc 4.5 kA
K60: Inc 6 kA C60: Inc 6 kA |
|
[Ui] rated insulation voltage |
440 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
4 kV
|
|
surge current |
250 A
|
|
contact position indicator |
No
|
|
control type |
Toggle
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
69 mm
|
|
product weight |
0.21 kg
|
|
colour |
White
|
|
mechanical durability |
5000 cycles
|
|
electrical durability |
AC-1: 2000 cycles
|
|
locking options description |
Padlocking device
|
|
connections – terminals |
Tunnel type terminals top or bottom 1…35 mm² rigid
Tunnel type terminals top or bottom 1…25 mm² flexible Tunnel type terminals top or bottom 1…25 mm² flexible with ferrule |
|
wire stripping length |
16 mm for top or bottom connection
|
|
tightening torque |
3.5 N.m top or bottom
|